INIM FIRE SE138EHCN Electrochemical Hydrocyanic Acid Detector - 4÷20mA output and 4 relay outputs
- MT Code
- INM_SE138EHCN
- Manufacturer Code
- SE138EHCN
- Brand
- INIM FIRE
Hydrocyanic Acid Detector (electrochemical). 4÷20mA output and 4 relay outputs. Measurement range 0÷10 ppm. ATEX ZONE 1
Gas detectors in explosion-proof enclosure for use in areas with the presence of potentially explosive atmospheres, certified CESI 03 ATEX 323 X (EN60079-0 and EN60079-1) are characterized by the following ATEX marking (Directive 2014/34/EU)
12÷24Vcc power supply - Atex marking: II 2G Ex d IIC T6 Gb - No. 3 solid state alarm relay. MAX 24V/1A SPST resistive load - No. 1 solid state fault relay. MAX 24V/1A SPST resistive load - Alarm levels (Relay) programmable via Dip-Switch - No. 1 linear output 4÷20 mA - Polarized plug-in terminals
Gas detected: Hydrocyanic acid - Cartridge change: ZSEHCN/EX - Measuring range: 0÷10 ppm - Calibration bottle: BO479 - Average life in clean air: 2 years
Codice Produttore | SE138EHCN |
---|---|
Brand | INIM FIRE |